A concentrator that uses 4G, Cat.1 communication with the acquisition system for uplink and RS-485 communication with the energy meter for downlink.
1. The uplink adopts 4G, Cat.1 and data acquisition system communication, with communication protocol Q/GDW376.1-2013.
2. RS485 communication is used for downstream communication with the energy meter. Different baud rates (1200, 2400, 4800, 9600) of energy meters can be mixed under RS-485, and up to 30 energy meters can be connected. The total length of a single RS-485 communication line shall not exceed 100 meters.
3. Communication protocol for downstream energy meters: Supports DL/T6452007 protocol commands.
4. Support 485 local setting/querying of concentrator communication parameters.
Main Technical Parameters
| Rated Voltage | Single Phase 220V |
| Power Frequency Magnetic Field | 400A/m |
| Impulse Voltage | 6kV |
| Electrostatic Discharge | 8kV |
| Fast Pulse Group | Power Circuit 5kV |
| Signal Circuit 2kV | |
| Surge | Common Mode 4kV |
| Differential Mode 2kV | |
| Operating Temperature | -40~+70℃ |
| Relative Humidity | ≤95% |
| Voltage Range | Rated Voltage ±20% |
| Frequency Range | 50Hz ±5% |
| Total Power Consumption | ≤3W |
| Overall Dimensions | Length × Width × Height:160mm×112mm×71mm |
| Weight | About 0.6kg |
| Power Outage Data | ≥10 Year |
| Hardware Interface (Standard Configuration) | RS-485 Interface |
External Structure Of HZZD-SII D-Type Concentrator

HZZD-SII D-Type Concentrator Wiring Diagram