The DTSU3579 three-phase rail multi-function energy meter adopts the latest design of special digital integrated circuits and ultra-low power consumption 16-bit MCU, which can directly and accurately measure the positive and negative power of the composite phase, the four-quadrant reactive power and the positive and negative power of each phase. It can carry out 4 rates, 14 time zones, 14 daily periods (8 sets), 30 holidays and weekends and holidays, etc., with the function of recording the maximum demand of active power, real-time measurement and processing of active power, reactive power, voltage, current, power factor and other electricity consumption parameters, with 1 RS485, with Functions such as power pulse output. The data display adopts a large-screen Chinese liquid crystal with a wide temperature range, which is convenient for manual meter reading and recording.
●Support 12 energy settlement freeze data;
●The demand data can be cleared through the zeroing function of the electric meter or the maximum demand zeroing function;
●There are two sets of rates and times that can be arbitrarily programmed, and another set of rates and times can be used from the set time point;
●The maximum demand can be zeroed by the programmer to issue a clear demand command in the programming state;
●This product is manufactured by SMT technology and advanced equipment, and strictly controls the process technology and quality in accordance with ISO9001: 2000;
●Highly integrated design and a variety of anti-interference designs such as anti-static, lightning protection, transient interference suppression, etc. The key components are all low-power and long-life devices of well-known international brands. Anti-deformation, anti-corrosion, anti-aging, good insulation and sealing performance;
●The performance index of this meter meets the technical requirements for multi-function electricity meters in the DL/T 614–2007 and GB/T17215.301-2007 standards, and the communication regulations comply with the DL/T645–2007 protocol and its filing documents;
●Use environmentally friendly lithium batteries as the clock backup power supply; the clock backup power supply does not need to be replaced during the life cycle of the electricity meter, and the correct working time of the internal clock is maintained for no less than 5 years after power outage; when the battery voltage is insufficient, the LCD of the energy meter displays the battery alarm symbol;
Parameter Description
Project | Technical Specifications |
Accuracy Level | Merit: Level 1, Level 2 |
Start The Operating Current | 0.004In(1级) 无功 0.005In(2级) |
Reference Voltage | 3×220/380V 3×57.7/100V(Three-Phase Four-Line) 3×100V(Three-Phase Three-Line) |
Rated Current | 3×1.5(6)A、3×5(20)A、3×10(40)A、 3×15(60)A、3×20(100)A |
Rated Frequency | 50Hz |
Latent | With Anti-Siltation Logic Design |
Weight | About 0.6kg |
Normal Working Temperature | -25℃~+55℃ |
Maximum Working Temperature | -30℃~+60℃ |
Storage And Transportation Temperature | -40℃~+70℃ |
Relative Humidity | ≤85% |
External Size | 126mm×90mm×74.5mm |
Technical Indicators
| Classification | Reference Voltage(V) | Maximum Current(A) | Active Pulse Constant(imp/kWh) | Non-Power Pulse Constant(imp/kvarh) |
| Three-Phase Three-Line | 3×100 | 6 | 20000 | 20000 |
| Three-Phase Four-Line | 3×57.7/100 | 6 | 20000 | 20000 |
| 3×220/380 | 6 | 6400 | 6400 | |
| 20 | 800 | 800 | ||
| 40 | 400 | 400 | ||
| 60 | 400 | 400 | ||
| 100 | 200 | 200 |
Working Parameters Of The Rate
| Clock Accuracy(Daily Error) | Battery Capacity | Data Retention Time After Power Outage |
| ≤0.5S | ≥1000mAh | ≥10 Years |