A type of upstream communication uses 4G+Ethernet to communicate with the server, and a downstream 485 concentrator.
1. The upstream communication adopts Ethernet, 4G, Cat.1 and the acquisition system, with communication protocol Q/GDW376.1-2013
2. The downstream uses RS-485 to communicate with the energy meter, with a total of three channels. Each RS-485 channel can be mixed with energy meters of different baud rates (1200, 2400, 4800, 9600). Each RS-485 can connect up to 32 energy meters, and the total length of a single RS-485 communication line should not exceed 1000 meters.
3. Communication protocol for downstream energy meters: Supports DL/T6451997 and DL/T6452007 protocol commands.
4. Freezing function: Automatically freeze the frozen data of measurement points for the collection system to read. The frozen data items include F161B frozen forward active energy indication and F163 frozen reverse active energy indication.
5. Big data storage: Each measurement point can store frozen data for 31 days.
6. Support USB setting/querying concentrator communication parameters.
7. Supports USB upgrade and Ethernet remote upgrade.
8. Equipped with a hardware clock, it can ensure the long-term accuracy and stability of the concentrator clock.
9. Local maintenance/setting communication method: Bluetooth (optional).
10. Data collection function: capable of collecting data from 485 meters using communication methods. The communication protocol between the concentrator and the electricity meter is transparent forwarding. The concentrator does not perform protocol conversion and directly forwards the commands issued by the system to the meter, and forwards the meter's response to the system.
11. Concentrator maintenance function: Three way 485, supports setting concentrator parameters; Supports 4G remote, USB, Bluetooth local reading/parameter setting; Supports 4G remote and USB local upgrades.
12. Alarm function: Real time monitoring of on-site operation status and timely notification to the operation and maintenance server upon discovery of abnormalities. Equipped with the following alarm functions: communication line abnormal alarm, equipment malfunction alarm; Support concentrator power outage alarm function.
Voltage Range | 220VAC |
Operating Temperature | -40~+70℃(Battery Operating Temperature-15~+45℃) |
Relative Humidity | ≤95% |
Total Power Consumption | ≤3W |
Overall Dimensions | Length, Width, Height:160mm*112mm*71mm |
Weight | About 0.3kg |
Hardware Interface (Standard Configuration) | Usb Port (Local):1 路 Ethernet Interface:1 路 485 Interface:3 路 Bluetooth Interface:1 路 |
485 Interface | Voltage:36V Current: Maximum Load Per Circuit 350ma |
Ethernet Communication Module | 10/100M Adaptive |
Topology Diagram

Top View Of Electric Meter Concentrator

Side View And Back View

Rear View Of Concentrator