Single phase gateway energy meter DDZY3579-Z is used to measure AC single-phase active energy with a rated frequency of 50Hz, achieving the management function of paying before using electricity. This product is manufactured using internationally advanced specialized ultra large scale integrated circuits and SMT technology. Key components are made of internationally renowned brands of low-power and long-life devices. The overall design adopts various anti-interference technologies to improve the reliability and service life of the product. The data display adopts a large screen Chinese LCD for easy meter reading.
●This product can directly and accurately measure the positive and negative active power, and perform multi rate measurement based on the corresponding rate settings. It can store the total energy and energy data of each rate for the past 12 settlement days;
●Equipped with event recording function;
●Supports 14 annual time zones, 8-day time slot tables, 14 day time slots, and 4 types of rates;
It also has infrared, RS485 communication functions, carrier communication, and can achieve remote meter reading. The communication protocol follows DL/T645-2007;
Its performance indicators comply with GB/T 17215.321-2008 and GB/T18460.3-2001 standards;
●Freezing function
Timed freezing: Freeze electrical energy data according to the agreed time and interval; Save each frozen amount 12 times;
Instant freeze: Freeze the current calendar, time, all electrical energy, and important measurement data under abnormal conditions; Instantaneous freezing saves the data from the last 3 times;
Agreed freeze: When converting between the new and old sets of rate/time period tables and time zone tables, if the power company deems it necessary, the energy and other important data at the time of conversion will be frozen, and the last two frozen data will be saved separately;
Daily freeze: stores electrical energy at midnight every day and can store data for two months;
Whole hour freeze: stores the total active energy at the whole hour or half hour, and can store 96 data points;
●Transfer on settlement date
The monthly electricity settlement date and hour can be set by the manager as needed, and the monthly rates and total accumulated active electricity can be settled at zero minutes and seconds on the set electricity settlement date and hour;
Gateway function: Collect other electricity meters through a foolproof communication interface;
●Communication method: uplink communication: CAT. 1, local communication: BLE Bluetooth, downlink communication: RS485;
Parameter description
Project | Technical parameter |
Accuracy level | Merit: Level 1, Level 2 |
Starting working current | ≤0.4%Ib(Directly connected) |
Power consumption of voltage line | Non-communication status≤0.5W、Communication status≤3W |
Current line power consumption | ≤1VA |
Clock accuracy(23℃) | ≤0.5 seconds/day |
Normal operating temperature | -25℃~+65℃ |
Maximum working temperature | -40℃~+70℃ |
Storage and transportation temperature | -40℃~+70℃ |
Relative humidity | ≤95% |
External size | 160mm×112mm×71mm |
Specification and model
| Model/Specification | Accuracy level | Rated voltage(V) | Maximum current(A) | Pulse constant(imp/kWh) |
| DDZY3579-Z | 2.0 | 220 | 60 | 1200 |
Technical indicators
| Load current | Power Factors | Basic error(%) | |
| Level 1.0 | Level 2.0 | ||
| 0.05Ib~0.1Ib | 1.0 | ±1.5 | ±2.5 |
| 0.1Ib~Imax | 1.0 | ±1.0 | ±2.0 |
| 0.1Ib~0.2Ib | 0.5L 0.8C | ±1.5 | ±2.5 |